MAWP (maximum allowable working pressure)

The highest gauge pressure a finished boiler or pressure vessel may run at, measured at its top, at a stated temperature, worked out from the thicknesses actually used less corrosion. The relief device is set at or below it.

Pujan Motiwala · · Updated

It matters because the relief valve, the hydrostatic test and the nameplate all follow from it: the hydro test is at least 1.3 times it for a Section VIII Division 1 vessel. Standard plate is often thicker than needed, so MAWP can be higher than the design pressure; worked from ⅜ in plate, a 48 in shell designed for 150 psi allows about 168 to 175 psi.

How it relates to design and operating pressure is in MAWP and design pressure; the shell thickness calculator works it back from a thickness, and the hydrostatic test calculator takes it forward.