Hydrostatic test

The pressure test of a finished boiler or vessel filled with water, held above its MAWP and inspected for leaks: at least 1.3 × MAWP (times a stress ratio) for an ASME Section VIII Division 1 vessel, 1.5 × MAWP for a Section I boiler.

Pujan Motiwala · · Updated

It is the last hold point before a stamped vessel or boiler ships: the Authorized Inspector witnesses it, and the test pressure goes on the data report. Getting it wrong is easy: the pressure is measured at the top, a gauge at the bottom reads higher by the water head, and the gauge's dial must be between 1.5 and 4 times the test pressure (UG-102).

A calculator, worked examples and the procedure are in the hydrostatic test guide. Under IBR in India the hydraulic test record goes with the registration documents.

Talk to us about your systems.

Tell us what's held together with workarounds right now. We reply to every message ourselves.