US and Canadian boiler laws: who requires ASME

The ASME Code isn't a federal law in the US. States, some cities and Canadian provinces make it law by adopting it in their own boiler and pressure vessel rules, often at a named edition, with their own scope, stamping, National Board registration and inspection rules. Some don't regulate pressure vessels at all. Check the jurisdiction where the equipment will be installed.

Pujan Motiwala · Written to the ASME BPVC 2025 Edition · checked against ASME's and the National Board's public pages on

A framed certificate on a wall board beside a boiler gauge glass and valve: a boiler's operating certificate.
Video chapters (10)
  1. 0:00Why ASME Code Is State, City & Provincial Law (Not Federal)
  2. 0:20How ASME Becomes Law: OH, MI, TX, CA & PA Keystone Rules
  3. 0:452026 NB-370 Synopsis: State ASME & NBIC Edition Lag Table
  4. 1:05U-Stamp Exemptions (FL, ID), NB Registration & Separate City Codes
  5. 1:28Joint Review Leaders (BPV-GUI-03 §3) & Canadian CRNs (CSA B51)
  6. 1:503-Step Pre-Order Flow: Chief Inspector, 5 Rules & PO Lock-In
  7. 2:1018 Official Excerpts Across 13 Primary Sources (NB-370, State & TSSA)
  8. 2:30Logging Code Edition & National Board Number Per Job in Boiler ERP
  9. 2:502025 Edition Copyright & Authorized Inspector Verification
  10. 3:00Next Steps: ASME vs. IBR 2026 (S26) & National Board Registration (S22)

Is the ASME Code required by law in the US?

Not federally: the Code gets legal force when a state, a city or a Canadian province adopts it in its own boiler and pressure vessel rules. Pennsylvania's rule is typical in form: "The Department adopts and incorporates by reference the following codes", with the ASME Code on the list. The adopting rule then says which equipment is covered, which edition applies, who inspects it in service, and what must be stamped, registered or permitted before it runs.

Which ASME edition does each state require?

Each sets its own, and many lag the current 2025 Edition. The National Board's 2026 Synopsis lists the edition each jurisdiction reports (ASME edition, with the NBIC edition in brackets):

JurisdictionASME editionNBIC
AlabamaCurrentCurrent
Alaska2013Current
Arizona20072019
California2023Current (2004 for refineries)
Colorado20232023
Delaware2019Current
Florida20172017
Georgia20192021
Illinois20232023
Indiana20152019
Iowa20212021
Louisiana20042004
Maryland20192019
Massachusetts20212021
Michigan20192019
MinnesotaCurrentCurrent
Missouri20192019
New Jersey2015Current
New YorkCurrent–
North CarolinaCurrentCurrent
North Dakota20252025
Ohio20232023
OklahomaCurrentCurrent
Oregon20232023
Pennsylvania20102011
Rhode Island20252025
TennesseeCurrentCurrent
TexasCurrentCurrent
WashingtonCurrentCurrent
Wisconsin20102011
Wyoming1968–

The National Board adds its own caveat: "Synopsis data is subject to change", and users should consult the jurisdiction's chief inspector. Most of these rules govern what may be installed and inspected; a new item built to a later edition is often accepted, but confirm it in writing before you build. Code cases have their own column in the Synopsis, with some states accepting them only "on a conditional basis".

What do the state rules themselves say?

Five read in full on 6 November 2026:

  • Ohio: OAC 4101:4-3-01 (effective 1 July 2024) adopts Sections I to XI and the code case book at the 2023 edition, plus "amendments, supplements, and addenda subsequently published prior to issuance of the next edition".
  • Michigan: R 339.5204 (effective 3 May 2023) requires "A boiler, blow down vessel, and expansion tank" to be built to the 2019 edition and B31.1 2018. Its scope names those items, not pressure vessels in general.
  • Texas: 16 TAC §65.2 defines ASME as the Code, code cases and interpretations "adopted by the council of the society", with no year: effectively the current edition. The Texas rules are the Board of Boiler Rules', for boilers.
  • California: 8 CCR §453 defines the ASME Code with no edition, and §454(a) requires new air tanks to be "constructed, inspected and stamped in compliance with the ASME Code" and, except UM vessels, registered with the National Board.
  • Pennsylvania: 34 Pa. Code §3a.1 still defines the ASME Code as the 2004 edition with its cases and interpretations, older than the Synopsis entry, and §3a.21(b) requires the ASME stamp and the National Board registration number on every ASME boiler and unfired pressure vessel, plus a Pennsylvania keystone serial number.

Which states don't require the U stamp?

Those that don't regulate unfired pressure vessels. The National Board's stamping table (2024 Synopsis) lists the ASME stamps each jurisdiction requires: Florida, Louisiana, Montana, New Mexico, South Dakota and West Virginia list boiler stamps without U; Idaho lists none; Wyoming lists only U, U2, U3 and UV. A buyer in those states may still want the U stamp for insurance, resale or a plant standard.

Which states require National Board registration?

Many, in different ways. The stamping table lists the NB mark as a requirement for Arizona, North Dakota, Washington and West Virginia among others; Pennsylvania requires the National Board number on the stamping; California requires registration of new air tanks. ASME's handbook says registration "may be required by the legal authority of a state or municipality". See National Board registration.

Do cities have their own boiler rules?

Some large ones do. The Synopsis lists separate entries for cities and counties including Chicago, Detroit, Los Angeles, Miami and Miami-Dade, Milwaukee, New Orleans, New York City, Omaha, Seattle, Spokane, St. Louis and Washington, D.C., several with their own editions; New York City's entry is the 1986 edition. Check the city as well as the state.

Who leads a shop's ASME joint review in each state?

ASME's handbook says the jurisdiction appoints the team leader in Alaska, Delaware, Hawaii, Louisiana, Minnesota, Nebraska, Oklahoma, Texas and Washington; ASME appoints for Idaho, Wyoming, Puerto Rico, the Virgin Islands and all Canadian provinces; and the National Board appoints for the remaining states. See how to get the U stamp.

How does Canada regulate pressure equipment?

Province by province, with designs registered and given a Canadian Registration Number (CRN) under CSA B51. Alberta's ABSA handles national applications for "Boilers, Pressure Vessels or Fittings to be Registered in Multiple Provincial or Territorial Jurisdictions in Canada", and Ontario's TSSA guidelines for fittings (January 2026, citing CSA B51:24) require that "The Canadian Registration Number (CRN) shall be identified whenever physically possible." The National Board's tabulation shows most provinces requiring the ASME construction sections by law, with Québec the exception for most sections. Register the design in each province where the equipment will go before it is built.

How do I check a jurisdiction before ordering?

  1. Find the jurisdiction's chief inspector on the National Board's Synopsis page, which has an entry per state, province and city.
  2. Confirm: is this equipment in scope, which edition, is NB registration required, are code cases accepted, what inspection or permit before first use.
  3. Put the answers in the purchase order, so the data report and nameplate come out right the first time.

The National Board's members are those chief inspectors, which is why its Synopsis is the starting point. For buying from a shop outside the US, see buying from India.

What does our software keep for jurisdiction rules?

Our US boiler demo records the Code edition and National Board number on each job's ASME record package. The demo company is in Ohio, whose rule adopts the 2023 edition plus later supplements, while the demo files its jobs to 2025: a real shop would confirm the edition with its jurisdiction. See ERP for boiler and pressure vessel shops.

Quoted from the official text (18)

“registration of data report forms may be required by the legal authority of a state or municipality of the United States or province of Canada.”

ASME BPV-GUI-03, section 1

“(1) United States: Alaska, Delaware, Hawaii, Louisiana, Minnesota, Nebraska, Oklahoma, Texas, Washington”

ASME BPV-GUI-03, section 3

“(1) United States: Idaho, Wyoming, Puerto Rico and the Virgin Islands.”

ASME BPV-GUI-03, section 3

“Synopsis data is subject to change. Users are advised to consult the jurisdiction’s chief inspection officer to avoid misinterpretation and ensure compliance with regulatory requirements.”

NB-370 Synopsis page

“2026 National Board Synopsis of Boiler and Pressure Vessel Laws, Rules and Regulations”

NB-370 Synopsis, editions table

“***Except for refinery and oilfield locations require an R stamp.”

NB-370 Synopsis, stamping table

“* On a conditional basis. Contact the jurisdiction for specific details.”

NB-370 Synopsis, tabulation of codes

“The National Board members are the chief boiler inspectors representing most U.S. states and provinces/territories of Canada, as well as many major cities in the United States.”

NBBI About Us

“The board of building standards adopts existing published standards by year of issue as shown in "Table 4-3-01" of the Administrative Code as well as amendments, supplements, and addenda subsequently published prior to issuance of the next edition by the same authority”

Ohio Admin. Code 4101:4-3-01(B)

“A boiler, blow down vessel, and expansion tank must be constructed as prescribed by these rules and the ASME boiler and pressure vessel code, section I, II, III, IV, V, VIII, IX, X, XI, 2019 edition”

Mich. Admin. Code R. 339.5204(1)

“ASME--The American Society of Mechanical Engineers Boiler and Pressure Vessel Code, code cases, and interpretations adopted by the council of the society.”

16 Tex. Admin. Code § 65.2(4)

“ASME Code: The American Society of Mechanical Engineers' Boiler and Pressure Vessel Code.”

8 CCR § 453

“all air tanks for new installations shall be constructed, inspected and stamped in compliance with the ASME Code”

8 CCR § 454(a)

“The Department adopts and incorporates by reference the following codes:”

34 Pa. Code § 3a.4

“2004 edition and its published cases and interpretations issued by ASME.”

34 Pa. Code § 3a.1, definition of ASME Code

“A boiler or unfired pressure vessel built to the ASME Code must be stamped with the appropriate ASME symbol, the manufacturer’s information in accordance with stamping requirements of the code of construction, and its National Board registration number.”

34 Pa. Code § 3a.21(b)

“Boilers, Pressure Vessels or Fittings to be Registered in Multiple Provincial or Territorial Jurisdictions in Canada”

ABSA, CRN application form

“The Canadian Registration Number (CRN) shall be identified whenever physically possible.”

TSSA, Fittings Guidelines (January 2026)

WPS and PQR registers, welder continuity, heat numbers from receipt to nameplate, and the data report package: the records a Code shop keeps, in one system.

A boiler manufacturer's system, from enquiry to dispatch and the IBR folder, with sample logins: try the live demo.

A boiler and pressure vessel shop's system, from inquiry to shipping and the ASME data report package, with sample logins: try the live demo. Fixed price, scope agreed before work starts: see the prices.

Official sources

What this page is not

A guide written by Ahrom Labs, not engineering advice, and not yet reviewed by an Authorized Inspector. The ASME Code is copyrighted and sold by ASME: paragraphs are cited by number and explained in our own words, never reproduced. Check every figure against your copy of the 2025 Edition and with your Authorized Inspector before relying on it. Last updated .

Talk to us about your systems.

Tell us what's held together with workarounds right now. We reply to every message ourselves.